Current Location > Home > Product > Details
MS-IOM6610-0
MS-IOM6610-0
Supply voltage: 24V AC,50Hz
Power consumption: < 5 VA
Input: 4AI 2DI
Onput: 4AO 2DO
Dimensions (L × W × H): 164×150×53 mm
Weight (NET): 0.25kg
Ambient conditions : Operating: 0~50℃,10~90% RH
Electrical standards: 2004/108/EC
Protection class: IP20(IEC529)
Ordering code: MS-IOM6610-0

MS-IOM6610-0 supports 2 Binary Inputs and 2 Binary Outputs 4 Analog Inputs and 4 Analog Outputs.

MS-IOM6610-0 can serve in one of three capacities, depending on where it is installed in the Metasys system.

 

When installed on the Sensor/Actuator (SA) Bus of a Field Equipment Controller (FEC), Advanced Application Field Equipment Controller (FAC), and IOM expands the point count of these controllers, which can be programmed in CCT.

When installed on the Field Controller (FC) Bus, IOM can be used as I/O point multiplexor to support monitoring and control from a Network Automation Engine (NAE) or Network Control Engine (NCE), which needn’t be programmed in CCT, only scanned in NAE/NCE and programmed in LCT.

When set Modbus slave mode, installed on Modbus bus of CSGW-Lite, IOM can integrate into NAE/NCE through BACnet IP and programmed in LCT.